Evaluation of ventilation options for an urban childcare centre

  • AUTHORS
    Bandara, Sanuj
    Andamon, Mary Myla
  • CATEGORIES
    2024 Conference Papers

Extract

Abstract: Thermal environments and ventilation are key considerations in the design of schools and childcare centres with children particularly sensitive and especially vulnerable to environmental contaminant exposures. Studies show that school environments generally exhibit issues of overheating, poor indoor air quality and inadequate outdoor air ventilation, attributed primarily to ineffective ventilation and air conditioning systems. This paper is a proof-of-concept evaluation of three (3) ventilation options – natural ventilation, mixed mode and mechanical ventilation for a proposed childcare centre using building simulations and assessed the effects on thermal comfort, indoor air quality and energy consumption. Simulation results indicate all three ventilation strategies achieved acceptable thermal comfort and mechanical ventilation as most effective with a median PMV of -1.0 in summer. Natural ventilation was shown to be superior in maintaining indoor air quality, with maximum CO2 concentration levels ranging 640-678 ppm. Even though mixed mode ventilation achieved optimal energy performance with the lowest cooling energy consumption, it required refinements to improve indoor air quality and thermal comfort performance. The findings will inform the development of guidelines on ventilation and air conditioning strategies in childcare centre designs for improved thermal comfort, optimal indoor air quality and energy efficiency.

Keywords: Ventilation strategies; thermal comfort; indoor air quality; childcare centres.