Assessing Indoor Climate and Mould Risks in Energy-Efficient Australian New Homes: A Comparison of AIRAH DA07 Continuous and Intermittent Conditioning Approaches

  • YEAR
    2025
  • AUTHORS
    Guan, Liqun
    Dewsbury, Mark
    Wallis, Louise
    Künzel, Hartwig
  • CATEGORIES
    2025 Conference Papers

Extract

https://doi.org/10.65388/HRVP8201

Abstract: Energy-efficient building design has emerged as a key strategy in addressing the global climate crisis.
However, growing evidence suggests that such buildings can reduce indoor climate resilience, particularly due
to interstitial moisture accumulation and mould growth. Transient hygrothermal and bio-hygrothermal
simulations can inform building envelope design to mitigate moisture and mould related risks. To support the
development of hygrothermal simulation methods, Australia has drawn upon international standards, which
prescribe continuous indoor conditioning regimes with stable temperatures and relative humidity levels.
However, this assumption does not reflect typical Australian conditioning patterns, where the mix of climatic
and cultural factors has led to intermittent heating and cooling practice. This study explores this discrepancy by
comparing continuous conditioning with intermittent conditioning regimes and their impact on hygrothermal
and bio-hygrothermal simulation results. This article reports on the results for timber-framed and compressed
fibre cement sheet clad external wall systems within three climate types. The results reveal that intermittent
conditioning can frequently lead to prolonged periods where indoor relative humidity exceeds 70% and indoor
air temperatures are often below 20°C, depending on room type, orientation, and outdoor climate. The results
indicate substantially higher risks under intermittent conditioning scenarios, with indoor mould growth
predominantly occurring in bedrooms and open-plan kitchen–living areas. Mitigation confirmed under
continuous conditioning was found to be inconsistent and generally less effective. These findings underscore
the importance of developing locally calibrated indoor climate assumptions to improve the accuracy of
simulation outcomes and better safeguard occupant health in Australia.

Keywords: Intermittent conditioning; AIRAH DA07; bio-hygrothermal performance; compressed fibre cement
sheet-clad timber-framed external wall (CFCS).